Did the pump always cycle? when it does cycle, what is a lot? I didn't say short cycle or fast cycle which are different issues.
You say with the pump off the pressure decreases. This would be due to a gradual loss of pressure as the pressure drops from cut-out to cut-in pressure. You ganged a set of valves to keep the pump running, you might of masked the problem, maybe not.
Clock the amount of time between cut-out and cut-in and the size of the drawdown of the pressure tank.
Calculate the demand requirements of the zone and if they don't jibe you may have a cracked pipe that opens and closes.