Lawn Care Forum banner
1 - 9 of 9 Posts

jvanvliet

· Registered
Joined
·
3,942 Posts
Discussion starter · #1 ·
Howdy all:

I service a site with 72 1" Irritrol 205t valves installed about 2 years ago. City water 3/4" meters @ 45 PSI.

Had excellent coverage until recently. Have very low pressure to the spray heads on some zones and excellent pressure on others. I'd say 40 zones are exhibiting low pressure, some intermittently.

Association called out the installer. Installer advised them to replace the diaphragm's to the affected valves.

Is this a normal issue for these valves? I've rarely had to replace a diaphragm unless damaged by debris, even dirty water valves.
 
I'd make sure that nothing is lodged in the solenoid discharge port first. Also, I have seen faulty controllers and wiring cause that problem before but not very often.
The older 205's had a grey nut on the diaphragm, which caused a lot of failures out here.
I did have a few recent problems with 205's where the diaphragm was not installed properly when the valve was built. I did get free replacements from the distributor for those since they were damaged during manufacturer assembly.
 
Only 2 years old and over half the diaphragms are bad, doesn't sound right to me. Sure the poor performing zones weren't over gpm to begin with? Is the 45 psi before the backflow? if so that's not a lot of flow with a 3/4 meter. Check the nozzling on the low pressure zones and see how much it adds up to.

I just noticed you mentioned meters as in plural. Is there an association with low performing zones and specific meters? Just a thought.
 
Did you see the excellent coverage until recently, or have you been told there was excellent coverage?

You said some zones exhibit low pressure. Have you checked the actual pressure reading at the head on both the good zones and the bad zones.

Also, have you compared how much volume/gpm the zones are designed for, good and bad zones. Adding up the gallons for that zone, or watching the meter as the zone runs.

What type of backflow and have you done the pressure loss calculations for the system?

You could fix one zone and see if it works, but an over 50% failure rate seems odd, in two years.

Are all the bad zones on one meter or mixed. Check the meter to see if it's open all the way.

I have seen the 205 act like that over the years, but it was one in a group. And a diaphragm and solenoid swap fixed it.
It just seems like something else is going on.
 
1 - 9 of 9 Posts